Chapter 24.65 Sidewalk Vault Openings

24.65.010 Location of Sidewalk Vault Openings.

The outer edge of all openings constructed in sidewalks for fuel, elevators, stairs, or other purposes shall be located not less than 2 feet from the curb line and the inner edge of any sidewalk opening will not be any closer than 3 feet to the property line.


24.65.020 Number of Sidewalk Vault Openings.

There shall not be more than one opening for each individual building frontage and in no case openings closer than 25 feet to an existing sidewalk opening.


24.65.030 Sidewalk Elevators.

Openings in sidewalks provided for in Section 24.65.010 shall be supplied with doors attached to a frame built into the sidewalk and shall be capable of supporting a load of 100 pounds per square foot. The door shall be constructed of sheet steel or other approved metal which has an approved non-slip surface. The dimensions of the door in any direction shall not exceed the dimension of the opening by more than 6 inches. The doors and frames shall be so constructed and maintained that there is no projection above or below the sidewalk exceeding 1/4 inch and existing doors which do not conform to the requirements shall be changed to conform within a period of 10 days after notice is given to change the same. Sidewalk doors shall be provided with a metal guard which, when the doors are open, will hold the doors open. This guard shall be located on the side of the sidewalk opening nearest the property line. The guard shall be made in the form of a grating with openings not exceeding 6 inches in dimension and so arranged that a child cannot get under or through the guard. This guard shall not be required for doors having metal gratings which are level with the sidewalk when the doors are open and the elevator platform is below the sidewalk level. Such gratings shall be capable of supporting a load of 100 pounds per square foot. Elevators having these sidewalk gratings shall be provided with a 3/4-inch steel bar to hold the doors open.


24.65.040 Operation of Sidewalk Elevator.

A. When not in operation the elevator shall be kept in its down position and the sidewalk doors shall be closed.

B. When the elevator is being raised, pedestrians shall be warned of the fact by an automatic warning device approved by the Director.

C. The sidewalk elevator shall not be raised sooner than 15 minutes prior to a delivery and shall be placed in a down position and the sidewalk doors closed within 15 minutes of the completion of a delivery.


24.65.050 Plans Required.

The construction of sidewalk vaults shall be considered as part of a building and plans shall be submitted showing the construction of the same.


Title 24 Building Regulat
Chapter 24.10 Administration and Enforcement
Chapter 24.15 Definitions
Chapter 24.20 Special Inspections
Chapter 24.25 Movings of Buildings
Chapter 24.30 Home Occupations
Chapter 24.35 Historical Buildings
Chapter 24.40 Use of and Projections Over Public Streets and Property
Chapter 24.45 Parking and Driveway Surfaces
Chapter 24.50 Flood Hazard Areas
Chapter 24.51 Wildfire Hazard Zones
Chapter 24.55 Building Demolition
Chapter 24.60 Fences
Chapter 24.65 Sidewalk Vault Openings
Chapter 24.70 Clearing, Grading and Erosion Control
Chapter 24.75 Uniform Building Address System
Chapter 24.80 (Repealed)
Chapter 24.85 Seismic Design Requirements for Existing Buildings
Chapter 24.90 Manufactured Dwelling Installation and Accessory Structures, Manufactured Dwelling Parks, Recreation Parks, Recreational Park Trailer Installation and Accessory Structures
Chapter 24.95 (Repealed)