8.32.080 Fire Protection.

Every court shall be provided with a water main not smaller than 2 inch pipe size, connected to the City water supply and having approved outlets, valves, hose connections, etc., for a 1‑1/2 inch fire hose, with the outlets so arranged that with a length of hose not exceeding 75 feet, a stream of water will reach every portion of the court.  The water main shall not be less in pipe size than the size given in the following table, based on the number of 1‑1/2 inch hose outlets served.

 
Number of Outlets
Not to Exceed
Pipe Size
In Inches
 
 
2
2
4
2 1/2
6
3
8
3 1/2
10
4
 

No rubbish or trash shall be burned in open fires.  No bonfires shall be permitted.  Incinerators shall be located and constructed under the direct supervision of the Fire Marshal.

All fire protection equipment shall be maintained in serviceable condition under the direction of the Fire Marshal.